Add to Cart
Description:
1. On-Off / 3-step dimming function for LED ceiling and tri-proof light
2. Integration of microwave motion sensor, daylight
3. Automatic switching and dimming based on motion and light level
4. Output current can be set via DIP switch
5. Unique design with mini sensor detector makes the drivers suitable to fix within compact luminaries
6. Stand-by power ≤1W
7. Detection area, Stand-by dimming level, time delay and daylight threshold can be precisely set via DIP switch
Specifications
Input | Operating Voltage | 198-264V AC 50Hz/60Hz |
Input Voltage | 220-240V AC 50Hz/60Hz | |
Input Current | ≤0.385A (230VAC@Full Load) | |
Power Factor | ≥0.90 @230VAC (Full Load) | |
Standby Power | ≤1W | |
Efficiency | 87% Max. @230V AC (Full Load) | |
Wiring Method | Screw terminal block (0.75-1.5mm2) | |
Output | Operating mode | Constant Current |
Load type | LED | |
Ripple requirement (Flickering or Flickering Free) | Flickering | |
No-load output voltage | 65VDC Max | |
Load output voltage range | 35-55V DC | |
Full load output power | 66W Max | |
Load output current | 800mA/900mA/1050mA/1200mA | |
Constant current/voltage Precision | Constant Current Precision ±5% | |
Wiring method | Press fit terminal, WireDiameter:0.75-1.5mm2 | |
Control Method | Sensitivity shift | 25%/ 50%/ 75%/100% |
Hold Time | 5S/90S/ 5min/ 25min | |
Stand-by brightness | 0%/ 10%/ 25%/ 50% | |
Stand-by period | 1min/ 5min/ 25min/ +∞ | |
Daylight sensor | 10Lux/ 30Lux/ 50Lux/ 100Lux or 150Lux/Disable | |
Over voltage protection | Auto reset | |
No load protection | Auto reset | |
Short circuit protection | Auto reset | |
Operating Environment | Operating temperature/ humidity | -25…+50℃ Humidity : 85% (Non-condensing) |
Storage temperature/ humidity | -40…+80℃ | |
Outer Max. Temp(Tc) | 85℃ | |
Safety & EMC
| Isolation pressurization | 3750V AC 5mA 60S (Input “L N” Output “SEC+ SEC-”) |
EMC | EN55015 EN61547 EN61000-3-2 EN61000-3-3 | |
Safety requirement | EN61347-1 EN61347-2-13 | |
Certificate requirement | TUV RoHS | |
Others | IP rating | IP20 |
Protection level | Class II | |
Installation requirement | Independent installation | |
Outer dimension | 212L*42W*30H mm(Driver) 56L*20W*13H mm(Detachable Sensor) | |
Packaging requirement | PE Bag Clapboard Outer Carton(K=A) | |
Life | 30000Hr |
Wring Diagram:
Function:
Output Current Setting:
Output Current(mA) | S1 | S2 | S3 |
1200 | ON | ON | ON |
1050 | ON | ON | - |
900 | ON | - | - |
800 | - | - | - |
Sensor Setting:
Daylight sensor | S1 | S2 | S3 |
Disable | ON | ON | ON |
100Lux | ON | ON | - |
50Lux | ON | - | ON |
30Lux | - | ON | ON |
10Lux | - | - | - |
(Disable:The Daylight Sensor is disable and will not detect the daylight)
Stand-by Period | S4 | S5 |
1Min | ON | ON |
5Min | ON | - |
25Min | - | ON |
+∞ | - | - |
(+∞: The lights will be remained at a low light level all the time)
Sensitivity | S1 | S2 |
100% | ON | ON |
75% | ON | - |
50% | - | ON |
25% | - | - |
Hold Time | S3 | S4 |
5S | ON | ON |
90S | ON | - |
5Min | - | ON |
25Min | - | - |
Stand-by Level | S5 | S6 |
0% | ON | ON |
10% | ON | - |
25% | - | ON |
50% | - | - |